Incoming Power & Protection
Receives, protects, and isolates incoming power while coordinating protection at the system entrance.
Voltage: Up to 34.5 kV
Voltage Class: Up to 38 kV
Connection: Delta | Wye | Grounded Wye
Input Connection: Radial | Loop
Protection & Sensing: CTs | PTs | Arresters | CPT
Transformer
Transforms voltage to meet downstream distribution and application requirements.
Apparent Power: 112.5 – 5,000 kVA
Phase: 1 | 3
Frequency: 50 – 60 Hz
Winding Material: Aluminum (Al) | Copper (Cu)
Connection: Delta | Wye | Grounded Wye
Connection Type: Flush | Throat
Taps: ±2 @ 2.5% Standard
Impedance: 5.75% ±7.5% Standard
Liquid-Filled Options
HV BIL: 30 – 250 kV
LV BIL: 30 – 75 kV
Temperature Rise: 55C | 65C | 55/65C
Tank Construction: Sealed
Oil Type: Natural Ester | Mineral Oil
Mineral Oil: ONAN | ONAF | ONAN\ONAF
Natural Ester: KNAN | KNAF | KNAN/KNAF
Dry-Type Options
HV BIL: 100 – 200 kV
LV BIL: 10 – 45 kV
Temperature Rise: 80C | 115C | 150C
Insulation Class: H
Type: Cast Resin | VPI
Cooling Class: AA | AF | AA/AF
Controls & Integration
Low-Voltage Distribution (Switchboard)
Distributes transformed power to downstream loads through a configuration engineered around project requirements.
Voltage: 480 – 1,000 V
Voltage Class: Up to 5 kV
Main: Up to 6,000 AF
Service Disconnects: Up to 6
Connection: Delta | Wye | Grounded Wye
Output Configuration: Radial
Feeder Sections: Configured to customer requirements
One Unit. One Delivery. One-Day Installation.
Comprehensive capabilities from design to deployment
01
Design & Configuration
Work with our engineering team to specify the exact configuration for your needs.
02
Complete integration and comprehensive testing in a controlled factory environment.
03
Delivery & Commissioning
One-day installation with rapid commissioning and minimal site disruption.
Built for Real-World Deployment
EV Charging Infrastructure
Data Center Power
Renewable Energy